- 6*15A, 4*300V
- Aux DC (0-300V), DC measuring inputs
- 12 binary inputs, 8 binary outputs
- Adjustable threshold (0-400V) for binary inputs
- In-built analog monitoring and recording function
- Can be upgraded to support the test of IEC61850 complied relay
Current |
|
Range |
6 x 0~15A |
Power(typical) |
6x 150VA at 15A
3 x 240VA at 30A |
Accuracy (typical) |
<0.08% rd+0.02% rg.guar., at 0~15A |
Voltage |
|
Range |
4 x 0~300Vac 1x0~600Vac 4 x 0~±300Vdc 1x0~±600Vdc |
Power(typical) |
4x 75VA at 300V
3 x 100VA at 300V |
Accuracy (typical) |
<0.08% rd+0.02% rg.guar., at 0~300V |
Frequency |
|
Sine signal |
0.001 … 1000Hz |
Transient signal |
dc … 10.0kHz |
Accuracy |
0.3ppm |
Phase angle |
|
Range |
-360°~+360º |
Accuracy (typical) |
0.05º |
Auxiliary DC supply |
0~300V |
Power |
88W at 110V, 176W at 220V, |
Binary input |
|
Number |
8 |
Type |
0-400Vdc threshold or potential free |
Counter input | |
Number | 4 |
Sample rate | 20kHz |
Binary output |
|
Number |
4 |
Type | Relay |
Number | 4 |
Type |
Semiconductor |
Low level output |
|
Number |
12 |
Accuracy (typical) |
0.025% |
DC measurement |
|
Voltage measuring |
0…±10V |
Current measuring |
0...±20mA |
IEC61850 GOOSE |
optional |
Dimension |
360*157*367mm |
Weight |
20kg |